The parallel UPSs must be connected to one another via their
current sharing terminals
(see
Figure 25), using the current sharing cable supplied in the cable kit (see Figure 45). The kit
includes cables for current sharing between two, three or four Centric units in parallel.
Figure 45: Current-sharing cable
6.1.4 EPO and parallel operation
An EPO switch can also be used if you intend to operate multiple Centric units in parallel. An external n-
pole / N.O. EPO switch may be connected according to the connection schematic. EPO disconnection of
the parallel units
MUST BE SIMULTANEOUS!
EPO wiring and switch rating must be 5 A / 230 Vac.
6.1.5 Manual bypass and parallel operation
A manual bypass switch can also be used if you intend to operate multiple Centric units in parallel. An
external n-pole / N.O. switch may be connected according to the connection schematic. Manual bypass
transfer of the parallel units
MUST BE SIMULTANEOUS!