Centric Installation Guide, rel. 4.7
60
5.
Verify that each UPS’s output circuit breaker is in the OFF position
(CB5 in the connection
diagram).
6.
Turn on one of the systems. This system will become the “master” system. Wait until the
automatic startup procedure is complete
– you will see the main menu screen. It should read
“UPS ON, Normal mode”, and there should be no alarms present. (If there are active alarms,
resolve any problems before continuing.)
Figure 50: The main menu screen