MegaV2 250 Installation Guide, Release 2.2
22
1.3.1
Continuing first-time start-up process
1.
Turn ON the ac input and ac output circuit breakers on the rear of each power module.
2.
Turn ON the battery cabinet circuit breaker.
3.
On the
MegaV2 250
main menu, choose "Operation > Turn on/off > System on".
4.
Return to the main menu by tapping on the "house" icon in the upper left corner of the
MegaV2 250
screen.
5.
On the main menu screen, if the alarm symbol (a yellow triangle) is displayed, press the
alarm symbol to display the potential problems. Refer to the troubleshooting section of this
document to determine the proper response to the alarm indications.
Figure 20: The "alarms" icon indicates alarm conditions
6.
Perform a brief battery test to verify that the
MegaV2 250
is ready and able to operate in
battery mode when needed. To perform a battery test, from the main menu choose:
"Operation > Battery test > Test battery". After 1 minute, cancel the test by pressing
"Abort the test > OK".
7.
Verify that the ac output circuit breakers on the electrical board are OFF.
You can now connect a load device to the ac output, then turn ON the ac output circuit
breakers on the electrical board.
8.
Now you must update the last maintenance date. From the main menu, choose
"Setup > Time > Set last maintenance date". Click on the line that says "Last maintenance
date". Press "confirm", and enter the system password if prompted for it.
9.
Finally, to save the settings you have defined, from the main menu choose:
"Setup > Save and restore > Save settings > OK".