MegaV2 250 Installation Guide, Release 2.2
37
Figure 36: Status > Modules > Output
If the output voltage of one or more phases is
not
within 2 % of the system nominal output
voltage, then:
10.1
Navigate to "Setup > Modules > Ac output voltage adjustment".
10.2
Select the replacement module, and adjust the problematic phases up or down as
required.
10.3
Return to step 10 and repeat the verification and adjustment process until the
output voltage of each phase of the replacement module is within 2% of the system
nominal value.
11
.
Switch "ON" the output circuit breaker on the rear of the module.
12
.
The
MegaV2 250
controller must be informed that a new module has been added to the
system. On the LCD control panel, from the main menu navigate to
"Setup > System > Number of modules". Increase the total number of modules by one, and
if the modules is to be one of the redundant modules, increase the number of redundant
modules by one.
13
.
Navigate to the main menu screen. If the yellow, triangular "alarm" indicator is visible,
check the alarms and see if any of them are related to the new module. If there are no
related alarms, the module has been successfully added to the system.