Table 3: Outstanding alarm messages
ALARM
MESSAGE
Explanation
AC INPUT FAIL
Meaning:
The voltage of one or more of the input ac phases is out of range, or
there is no ac input at all. The UPS is now in Battery Mode.
Additional indications:
The alarm LED lights up and the audible alarm
sounds. The symbol
appears on the Ac Input screen.
Action:
If there is a power outage, it is advisable to save any critical open files
you are working on before the UPS battery is exhausted. See “In the event of
an ac power outage” on page 57. If there is not a power outage, check the
circuit breaker for the line supplying the UPS with power. The circuit breaker
may be off.
AC OUTPUT FAULT
Meaning:
The voltage of at least one of the output ac phases is out of range.
Additional indications:
The alarm LED lights up and the audible alarm
sounds. The symbol
appears on the Ac Output screen.
Action:
After a power outage, this message can be ignored.
This message could also be the result of an overload. Reduce the load on the
UPS; this may resolve the problem. If not, contact Technical Support.
BATTERY LOW
Meaning:
The battery will soon be fully discharged.
Additional indications:
The alarm LED lights up and the audible alarm
sounds. The symbol
appears on the main screen.
Action:
Shut down your computer or other equipment connected to the UPS.
BATTERY TEST
FAIL
Meaning:
The most recent battery test has failed.
Additional indications:
The alarm LED lights up and the audible alarm
sounds. The symbol
appears on the main screen.
Action:
It is possible that the most recent battery test occurred after a power
outage and before the battery had fully recharged. Wait until two hours have
elapsed from the most recent battery test and perform a manual battery test.
See “Manual battery test” on page 31.
BYPASS NOT
READY
Meaning:
The voltage of at least one of the bypass phases is out of range, and
a transfer to bypass mode cannot be made at this time.
Additional indications:
The alarm LED lights up and the audible alarm
sounds. The symbol
appears on the bypass screen.
Action:
This alarm can be the result of a power outage, in which case it can be
ignored. Otherwise, check the circuit breaker for the line supplying the bypass
voltage. The circuit breaker may be off.
END OF BACKUP
Meaning:
The batteries have been exhausted, and the UPS has turned itself
off.
Additional indications:
The UPS has turned itself OFF.
8 kVA, 208 V model:
The symbol.
appears on the main screen.
10 kVA, 400 V model:
The UPS screen is blank.
Action:
Wait for ac power to return. Then, if the UPS is in Auto Restart mode it
will start up automatically; otherwise, start the UPS manually by pressing the
OFF/ON button twice.