Gamatronic Electronic Industries Ltd.
User Guide: MEGA V2 SA25, Release 1.5
45
9.
A
UTOMATIC
R
ESTART
In the event of a prolonged power outage, the UPS turns itself off automatically after the
batteries have been exhausted. You can instruct the
Mega V2 SA25
to start up automatically so
that it will supply current to the load devices when the AC power is restored. This feature is
called
automatic restart
.
If you do not use the automatic restart procedure, when the AC power returns the recharging
process begins automatically, but no power is supplied to the load.
9.1
Determining the current automatic restart setting
To determine if the automatic restart mode is on or off, go to the PROFILE screen
To see the UPS Profile screen, from the
main screen
, press the
Down
button once.
The Profile screen shows the current Automatic Restart status.
9.2
Changing the automatic restart status
1.
From the main screen, press the
Ent
button to display the
main menu
.
2.
On the MAIN MENU, select
ADVANCED MENU
and press
Ent
.
3.
On the ADVANCED MENU, select AUTOMATIC RESTART and press ENT.