38
P+ Premium SA, 15 kVA, rel. 1.4
Figure 5: UPS rear panel view, with protective cover removed
7.
Run the
ac output cable
through the cable holder labeled “ac output” in Figure 5. Connect the cable
to the ac output terminals, also detailed in Figure 5. Use the appropriate grade of wire as specified in
Table 4 on page 36, or according to local electrical codes.
8.
Run the
ac input cable
through cable holder labeled “ac input” in Figure 5. Connect the cable to the
ac input terminals, also shown in Figure 5. Use the appropriate grade of wire as specified in Table 4
on page 36, or according to local electrical codes.
9.
Run the
batteries cable
through the cable holder labeled “Batteries” in Figure 5. Connect the cable to
the ac input terminals, also shown in Figure 5. Use the appropriate grade of wire as specified in Table
4 on page 36, or according to local electrical codes.
10.
Tighten all cable holders so that the cables are fastened securely.
11.
Connect the
PE-Ground cable
to the PE-Ground pin, shown in Figure 5.