P+ Premium SA, 15 kVA,
rel.
1.4
33
7.1.1
Cable connections for unit with NO manual bypass
This section describes cable connections for using the POWER+ PREMIUM SA 15 configuration
using the rear-panel adapter that DOES NOT HAVE a manual bypass switch.
For connections when
using the adapter
with
a manual bypass switch, see section
Only an authorized electrician may wire the UPS power connections.
Do not attempt to wire any of the power connections on your own.
To connect the required cables to the UPS for 3-3 usage:
1.
Use cables appropriate for the currents shown in Table 3 according to your local electrical codes.
2.
Ensure that the UPS’s input and output cables are equpped with circuit breakers appropriate for the
chosen cables.
Table 3: Wiring requirements for system w/o manual bypass sw.
AC output
(Gnd, N, L1, L2, L3)
Bypass input
(Gnd, N, L1, L2, L3)
Ac input
(Gnd, N, L1, L2, L3)
Battery input
3 x 21.7 A
3 x 21.7 A
3 x 27 A
A cable of 4 mm
2
cross-sectional
area is required. (Use the 1.5 meter-
long battery cable supplied by
Gamatronic.)
3.
Using a screwdriver, remove the cable cover from the rear of the POWER+ PREMIUM SA 15.