SINGLE UPS MODULE SPECIFICATIONS
Table
2-1 Single UPS Module Specifications
TECHNICAL DATA – UPS MODULE
Output Rated Power
10 kVA / 8 kW
Topology
Online Battery, Double Conversion
Construction
Modular parallel hot-plugged modules
Input Voltage (V)
3 × 400+N (3 × 230 V)
Input Voltage range (%)
-27 and +20
Input Current (A)
15 A
Input Frequency (Hz)
47–63 Hz
Frequency tracking range (Hz)
±1, ±2, ±3 (selectable)
Output slew rate
1 Hz/sec
Power walk-in (sec)
> 60
Input Power Factor
0.99
Input THDI (%)
5
Output Voltage (V)
3 × 400+N (3 × 230V)
Output Static Regulation (%)
±1
Output Regulation for unbalanced load (%)
±1 for 100% unbalanced load
Dynamic response to 100% load step (%)
2
110 % for 10 minutes
125 % for 60 seconds
Overload
1000 % for 1 cycle
Output Waveform
Sinusoidal
Output THD (%)
Less than 2 for linear load
Load CF (max)
6:1
Fuse clearance capability
Input, Output, DC link
AC-AC efficiency (nominal)
Up to 96 at full load
Maximum power dissipation (Po=8KW)
421 W (1437 BTU)
-10 to +40 (operating)
Ambient temperature (ºC)
-20 to +60 (storage)
Relative humidity (%)
95 max non-condensing
Altitude (m)
1500 w/o de-rating
DC-Link Voltage
±340 V to ±425 V
Cooling system
Forced air: multi-fan with speed control
Dimensions: W x H x D
19" x 2U x 455 mm (Excluding shelf)
Weight 9.5