Gamatronic Electronic Industries Ltd.
Power+ Technical Guide
75
B a t t e r y C h e c k s
Turn the battery circuit breaker to Off and disconnect all Anderson connectors in the battery set.
Record the battery serial number, type, and number of cells in the table below:
Battery
manufacturer
Battery model
Rating (Ah)
Number of strings (x 32)
Use a power resistor of 0.5
Ω
(300 W rating recommended) for the load to check the voltage drop across the
terminals of each battery. There should be no more than a 10 Vdc drop for any battery.
Replace any batteries that seem to be inadequate.
BATTERY STRING #1
BATTERY STRING #2
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
Batt.
no.
Good
Bad
1
17
33
49
2
18
34
50
3
19
35
51
4
20
36
52
5
21
37
53
6
22
38
54
7
23
39
55
8
24
40
56
9
25
41
57
10
26
42
58
11
27
43
59
12
28
44
60
13
29
45
61
14
30
46
62
15
31
47
63
16
32
48
64
END OF MAINTENANCE PROCEDURES REPORT