Gamatronic Electronic Industries Ltd.
Power+ Technical Guide
89
11.4.3 SCREEN
2
To access SCREEN 2 press the key ARROW RIGHT when SCREEN 1 is selected.
a) #OF PHASE: FORCE 3 for 3 phase output, FORCE 1 for single phase output or AUTO when the
mode is defined by DIP SWITCH of the modules.
b) REV: revision of system controller
’
s (SC) software
c) LVD BY AC FAIL: DIS (disabled) or EN (enabled). This function, if enabled, performs system
shutdown after 3 Hours of AC failure to prevent deep battery discharge by low current. In most
application the function must be DIS.
d) MAINT:
YEAR.MONTH.DAY:
date of last maintenance
e) TEMP. SENSOR: DIS or EN . External thermosensor is disabled/ enabled. In most applications
must be DIS.
f) SITE: the site identification number. Is used in network applications.
g) CURR.SENSOR: DIS or EN. Optional battery current sensor is disabled/ enabled. In most
applications must be DIS.
11.4.4 SCREEN
3
To access SCREEN 3 press the key ARROW RIGHT when SCREEN 2 is selected.
The screen presents status of controller board
’
controller card" beginning on page 33 for more information regarding these jumpers.
a)
Not HARD Silicon. Must be HARD only initially, during first activation of non-configured
controller. After production should be Not HARD Silicon.
b)
Silicon Mode. Regular mode allowing setups change. The setups are saved in EEPROM chip.
c)
CAPACITY HI (LO). High/low battery capacity mode when battery capacity is more/less than
100AH to achieve optimal resolution of battery current displayed value.
d)
No/Yes Rmt Pan. Outputs of SC are not configured/ configured for optional remote panel
connection.
e)
AC: 220V. Nominal AC input voltage: 220V for 2x32 batteries, 110V for 2x16 batteries in series.