Gamatronic Electronic Industries Ltd.
Power+ Technical Guide
105
15. SYSTEM SPECIFICATIONS
Table
15-1: Technical specifications
Power
+
TECHNICAL DATA
Topology
On line Battery, Double Conversion, VFI
Construction
Modular parallel hot-plugged modules
Operation Continuous
Input
Voltage (V)
3×
400
+N
Voltage range (%)
-27 and +20
Current (A)
3 × 15 A per module – no inrush current at startup
Frequency (Hz)
47–63
Power walk-in (sec)
>60
Power Factor
0.99
THDI (%)
5
Output
Rated Power
10 kVA / 8 kW to 100 kVA / 80 kW
Frequency (in free-running mode, Hz)
50/60 Hz ±0.1%
Frequency tracking range (Hz)
±1, ±2, ±3 (selectable)
Slew rate
1 Hz/sec
Voltage (V)
3×
400 +N
Static Regulation %
±1
Regulation for unbalanced load %
±1 for 100% unbalanced load
Dynamic response to 100% load step %
±2
Overload
110 % : 10 min.; 125 % : 60 sec.; 1000 % : 1 cycle
Waveform Sinusoidal
THD (%)
Less than 2 for linear load
Load CF (max)
6:1
AC-AC efficiency (nominal) %
Up to 96 at full load
DC-AC efficiency (nominal) %
Up to 98 at full load
Batteries
DC-Link Voltage (V)
±340 to ±425
Quantity
64 × 12 V
Type
Sealed, lead acid, rechargeable
General
Maximum power dissipation (Po=8KW)
N*333
W (N*1136 BTU)
Ambient temperature (÷C)
-10 to +40 (operating)
-20 to +60 (storage)
Relative humidity (%)
95 max non-condensing
Altitude (m)
1500 without derating
Enclosure IP20
Cooling system
Multi-Fan with speed control (forced)
Standards
EMC
EN50091-2 Class A; IEC 62040-2 Class A
Design
EN50091-3; IEC 62040-3
Safety
EN50091-1; IEC 62040-1-1
Low magnetic field radiation
EMF as per ICNIRP
Dimensions
UPS type
10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA 70 kVA 80 kVA 90 kVA 100 kVA
Height
(cm) 71 80 90 99 108 118 127 136 146 155
Width (cm)
59.8
Depth (cm)
67.3
Weight
(Kg) 84 99 114 129 144 159 174 189 204 219
Acoustic Noise
Noise (dBA)
with half load
48 52 53 54 55 55.8
56.4
57 57.5
58
Noise (dBA)
with full load
51 54 55 57 58 58.8
59.4
60 60.5
61