Table
9-1: UPS Module Indicators
CONDITION
LINE
(GREEN)
OUTPUT
(GREEN)
ALARM
(RED)
BEEPS
REMARKS
Wake-up
On On On
♫
Start
Off
Off
Off
About 1 minute
Normal
Operation
On On Off
Abnormal
Input voltage
Off On On
♫
One phase
abnormal input
Blinks On
Off
♫
High Input
Current
Blinks On
On
♫
Vdc > 450V
On Off Off
♫
High
Vdc
Vdc > 500V
On Off On
♫
Very high Vdc
DC imbalance
On On Blinks
♫
Low Vdc< 360V
On* On
Blinks
Vdc very low,
< 320V
On* Off
On
DC critical fail
< 200V
Blinks Off
On
* Mostly will be
caused by Vin
fault that will turn
off
LINE
LED
Circulation
Current
On Off On
Output overload
On Blinks Off
Output is
disconnected
On
Blinks
On
Result of output
overload
Communication
failed
On On On
♫
Or absence of
System
Controller
Output
short-circuit
Blinks Off
On
♫