Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
87
4.
Select
Set AC Alarms Hysteresis
:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT]
1> SET AC HIGH & LOW ALARM LEVELS
2> SET AC ALARMS HYSTERESIS
PLEASE SELECT 1
Figure 126: Ac alarms menu
5.
Use the arrow keys to set value, press
Ent
, and then
Esc
:
[Main Menu > SETUP > Ent > (password) > Ent > ALARM SET > AC VOLT > Set AC Alarms
Hysteresis]
SET AC VOLT ALARMS HYSTERESIS VALUE
(1 – 20) VOLT
05
Figure 127: Set ac voltage hysteresis
10.8.2
Setting Battery Floating Voltage Alarm
1.
Select
FLOAT VOLT
:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 128: Alarm set menu
2.
Select
BATEND
:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 129: Battery floating charge alarm setup menu