Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
166
19.
T
ECHNICAL SPECIFICATIONS
Table 24: Technical specifications for the RM100 3x208 Vac
POWER
+
TECHNICAL DATA
Topology
True On-line Battery, Double Conversion, VFI
Construction
Modular parallel hot-plugged modules
Operation
Continuous
Input
Voltage
3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Voltage range
+15 % and -25 %
Current
28 A per module – no inrush current at startup
Frequency
47 Hz–63 Hz
Power walk-in
> 60 sec.
Power Factor
0.99
THDI
5 %
Output
Rated power for 3-3 configuration:
10 kVA / 8 kW to 100 kVA / 80 kW
Frequency tracking range
±2 Hz
Slew rate
1 Hz / sec.
Voltage
3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Static Regulation
±1 %
Regulation for unbalanced load
±1 % for 100% unbalanced load
Dynamic resp. to 100% load step
±2 %
Overload
110 % for 10 min., 125 % for 60 sec., 1000 % for 1 cycle
Waveform
Sinusoidal
THD
Less than 2 % for linear load
Load CF
4:1
Ac-Ac efficiency (nominal)
Up to 94 % at full load
Dc-Ac efficiency (nominal)
Up to 97 % at full load
Batteries
Dc-Link Voltage
±160 to ±216 Vdc
Quantity (in optional external cabinet)
2 x 32 x 12 Vdc (40 Ah)
Type
Sealed, lead acid, rechargeable
General
Maximum power dissipation (Po=8 kW)
N*510 W (N*998 BTU), where N = # modules
Ambient temperature
operation (up to 80 kVA):
operation (90 and 100 kVA)
storage:
+14 to +104
°
F (-10 to +40
°C
)
+14 to +86
°
F (-10 to +30
°C
)
-4 to +140
°
F (-20 to +60
°C
)
Relative humidity
95 % max., non-condensing
Altitude
1500 m without derating
Enclosure
IP20
Cooling system
Multi-Fan with speed control (forced)
Standards
EMC
IEC 62040-2, under EMC 2004/108/EC
Design
IEC 62040-3
Safety
IEC 62040-1, under LVD 2006/95/EC
Low magnetic field radiation
EMF as per ICNIRP