Gamatronic Electronic Industries Ltd.
POWER+ RM100,
3
X
208
V, User Guide, 1.3
39
7.5
Fuses
WARNING!
To reduce the risk of fire, replacement fuses must be of the same type and rating as the
original.
AVERTISSEMENT !
Pour réduire le risque du feu, les fusibles de rechange doivent être du mêmes type et
estimation que l'original.
AC INPUT FUSES
Verify that the appropriate ac fuses are present.
In the ac distribution module, the input for each UPS module is protected by a 32A fuse for each phase, so
that each module, including the controller, has 3 fuses (one each for the L1, L2, and L3 phases). Ten
modules plus the controller would require 33 fuses, as illustrated in Figure 32. In the 100 kVA model the
fuse receptacles are numbered from right to left.
Figure 32: Ac input fuses (100 kVA model)