7.10
First-time Startup
This section describes the procedure for starting up the Power+ for the first time, after having completed
the installation process described in the previous chapter.
1.
Ensure that the maintenance bypass switch is set to NORMAL (OFF), and that no load devices are
connected to the UPS.
Note
: When applying power to the
POWER+
, the system automatically runs the startup
process without a need to press the On/Off button.
2.
Turn the ac input and ac bypass switch ON and wait (for about 2 minutes) for the
POWER+
to
initialize.
3.
The start-up sequence will begin and the control panel will show the following sequence. (The details
of the display may vary from what is shown in the illustrations below, depending on your system's
particulars.)
At start-up, the following screen sequence appears:
UPS POWER+
SC25270105
W E L C O M E ! ! !
Figure 36: Start-up screen 1
WARNING !!!
SYSTEM RUNNING IN:
S I L I C O N M O D E (JP2 – IN)
--------PLEASE NOTIFY SUPERVISOR--------
Figure 37: Start-up screen 2
In “SILICON MODE”, commands issued through the Power+ Control Panel are executed immediately.
Operators should exercise caution.
Note
: In Figure 37, “Silicon mode” indicates that the configuration jumper is installed, thus
allowing for modifications.
WAIT FOR RESULTS…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED
Figure 38: Start-up screen 3
S Y S T E M I N I T I A L I Z I N G
SC25270105
PLEASE WAIT FOR COUNT DOWN TO FINISH
45 SECONDS LEFT