7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
12
Specifications
System Overview
1.5 Specifications
The following list the specifications for the 7100 Series control panel.
Notification Appliance Circuits (TB1)
The following list the notification appliance circuits:
•
Two (2) regulated power outputs
•
Power-limited
•
Supervised
•
Non-coded
•
Max. alarm load 1.5 amp /circuit
For a list of Gamewell-FCI Approved, UL Listed notification appliances, refer to the
Compatibility
Addendum to Gamewell-FCI Manuals P/N 9000-0427
.
•
Form “C”
•
Rated 2A @ 30 VDC Resistive
Alarm signals latch in. Supervisory and System Trouble signals do not latch in.
Trouble Dry Contacts (TB2)
•
Form “C”
•
Rated 2A @ 30 VDC Resistive
Transfer Relay Control (TB2) (Special Application)
Transmit loss of AC power or brown out to Gamewell-FCI Model DRBC-1 battery charger.
•
Power-limited
•
Unsupervised
Signaling Line Circuits (TB3)
•
One (1) or two (2) Class “B”, Style 4 circuits
•
24 VDC nominal
•
Power-limited
•
Supervised
•
40 Ohm max. line resistance
•
0.5 µf max. capacitance
Capacity of 99 analog sensors and 98 addressable devices per circuit
Power Supply Output
Supervisory current 1.0 amp (max.) (24 VDC nominal)
Alarm current
3.335 amp (max.) (24 VDC nominal)
NOTE:
Use U.L. Listed End-of-Line Resistor EOL-N (47K), P/N 4700-0512 Alarm Dry Contacts
(TB2)