7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
39
Central Station Reporting
Basic System Module (BSM)
Table 3.9.2 lists the DACT Event Reporting Codes.
Event SIA
Contact
ID
4/2
3/1
Fire Alarm (Smoke or Manual Station)
FA GGT
1 110 00 GGT
0T
0
Fire Alarm Restored
FH GGT
3 110 00 GGT
2T
2
Waterflow Alarm
SA GGT
1 113 00 GGT
0T
0
Waterflow Alarm Restored
SH GGT
3 113 00 GGT
2T
2
Trouble (except Waterflow or Special AMM)
FT GG0
1 373 00 GG0
8T
8
Trouble Restored
FJ GG0
3 373 00 GG0
7T
7
Trouble (Waterflow AMM)
ST GG0
1 370 00 GG0
8T
8
Trouble Restored (Waterflow AMM)
SJ GG0
3 203 00 GG0
7T
7
Trouble (Special AMM)
UT GG0
1 370 00 GG0
8T
8
Trouble Restored (Special AMM)
UJ GG0
3 370 00 GG0
7T
7
Supervisory / Tamper (Module)
SS GGT
1 203 00 GGT
6T
6
Supervisory Restored (Module)
SR GGT
3 203 00 GGT
7T
7
PAS/Action/Supervisory (Sensor)
FS GGT
1 200 00 GGT
6T
6
PAS/Action/Supervisory Restored (Sensor)
FR GGT
3 110 00 GGT
7T
7
Disable (except Waterflow or Special AMM)
FB GG0
1 571 00 GG0
8T
8
Disable Restored
FU GG0
3 571 00 GG0
7T
7
Disable (Waterflow AMM)
SB GG0
1 570 00 GG0
8T
8
Disable Restored (Waterflow AMM)
SU GG0
3 570 00 GG0
7T
7
Disable (Special AMM)
UB GG0
1 570 00 GG0
8T
8
Disable Restored (Special AMM)
UU GG0
3 570 00 GG0
7T
7
AC Fail
AT 0
1 301 00 000
8T
8
AC Fail Restored
AR 0
3 301 00 000
7T
7
Phone Line 1 Fault
LT 1
1 351 00 000
81
8
Phone Line 1 Fault Restored
LR 1
3 351 00 0000
71
7
Phone Line 2 Fault
LT 2
1 352 00 000
82
8
Phone Line 2 Fault Restored
LR 2
3 352 00 000
72
7
Automatic Test (NORMAL)
RP 0
1 602 00 000
90
9
Automatic Test (With Exception)
RP991
1 602 00 991
91
9
For Contact ID and SIA Formats:
GG = group number assigned to the device, 00-99
(For networked systems, GG = Node number)
T = Type of device or event causing the event to be reported.
0= Non-loop event
1= Any event or device type not listed below
2= Manual Station
3= Supervisory Device (Non-latching)
4= Supervisory Device (Latching)
5= Waterflow (Non-silenceable)
6= Smoke Alarm
8= Multilevel Device
NOTE:
Special AMMs include the following functions:
Reset Switch, Silence Switch, Drill Switch, Alarm Acknowledge Switch, Trouble Acknowledge Switch.
Table 3.9.2 DACT-E3 Event Reporting Codes