7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
8
Features
System Overview
1.2 Features
1.2.1 Standard Features
The standard features for the 7100 Series fire alarm control panel are listed below:
•
Two (2) Class B, Style 4 Signaling Line Circuits
•
Two (2) Class B, Style Y Notification Appliance Circuits
•
Alarm and Trouble dry contacts
•
Accommodates 99 Gamewell-FCI Approved, UL Listed compatible analog sensors per SLC
•
Accommodates 98 Gamewell-FCI Approved, UL Listed compatible addressable
monitor/control devices per SLC
•
80-character alphanumeric LCD display
•
280 event history buffer (non-volatile) (4,000 events when the NGA Module is installed)
•
Power-limited
•
Resettable/Non-resettable 1.0 amp @ 24 VDC power output, FWR
•
Alarm verification
•
Walk test
•
Multi-level alarm processing
•
Positive alarm Sequence (PAS) operation
•
NAC coding
•
Trouble reminder
•
Integral RS-232 port
•
Key Switch - keyed alike with the door lock and renders the key pad inoperative until
activated.
1.2.2 Optional Features
The following list the optional features for the 7100 Series fire alarm control panel.
•
Class A Module (CAOM) with Disconnect Switches for NACs and SLCs
•
Digital Alarm Communicator (DACT) (Model 7100-D)
•
RS-232 Printer Transient Module (PTRM), Supervised
•
Municipal Circuit Option Module (MCOM)