System Programming
I/O Menu Selections
5.4 I/O Menu Selections
Table 5.4.1 and Table 5.4.2 lists the I / O menu selections and description. Figure 5.4.1 illustrates
the menu options.
Figure 5.4.1 I/O Menu
Menu
Descriptions
Output ON/OFF
Forces the toggling on or off of a specified output. These outputs can
include NAC 1, NAC 2, Municipal Circuit (if present) and any
Addressable Control Point.
Enable/Disable
Allows the user to take any addressable device on either SLC and
disconnect it through software. While disabled, a point will report a
trouble until it is enabled, but will not cause or respond to an alarm.
Table 5.4.1 I/O Menu Selections
I/O
OUTPUT ON/OFF
ENABLE/DISABLE
Menu Tree
Display and Selections
Main
Walk/Drill
[Walk/] 1: Drill (OFF) 2:Audble Test (OFF)
[DRILL] 3: Silent Test (OFF)
1: Toggles Fire Drill ON/OFF.
2: Toggles Audible Walk Test ON/OFF.
3: Toggles Silent Walk Test ON/OFF.
Main
I/O
[I/O ] 1: Output On/Off
[CTRL] 2: Enable/Disable Device
1: Opens Select Device to Control Menu.
2: Opens Select Device to Enable Menu.
NOTE:
These are the same menus as used in the Configure
section, or similar, except after selection they proceed to the
following menus.
Main
I/O
Select
Output On/Off
[CNTRL] NAC 1 (AUTO)
[L,AAA ] 1:On/Auto
1: Toggles selected output ON/AUTO.
Output selections include NAC1, NAC2, and Muni Circuit (if
present). These appear at the bottom of the output device scroll
list, and can be entered by keypad as addresses 0001, 0002,
and 0003. (Note that AOMs start at address 1101). If the
selected device is an AOM, its location is shown, otherwise
NAC 1, NAC2, or Municipal Circuit. Status LEDs and relays are
not considered to be programmable outputs.
Main
I/O
Select
Enable/Disable
[ENA/DIS] Municipal Circuit (ENABLED)
[L,AAA ] 1: Enable/Disable
1: Toggles selected device ENABLED/DISABLED
Table 5.4.2 I/O Menu Tree Display and Selections