Flex 620
Programming - Revision 5, 11/22/01
______________________________________________________________________________________________
91
Change Menu 2
Change menu 2 has options to change the City Tie operation, the Automatic Signal
Silence Timer, The Annunciator Supervision, The Trouble Relay operation and the
Automatic Dialer connection.
Change City
The City Tie Circuit is designed to operate in two modes of operation. Standard
mode and Chicago mode. In the standard mode alarms and troubles are transmitted
over the city tie circuit. In the Chicago mode the city tie transmits all troubles and
alarms with the exception of City Tie troubles. If the city tie circuit detects a trouble
condition the Spare relay will transfer for use with a local indicator that indicates
troubles and alarms can’t be transmitted.
Change Menu (Misc.)
1=Menu1 2=Menu2
0=Exit
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>1
Press Enter Key To Exit
Press Any Other Key To Toggle
City Tie Is In Standard Mode
City Tie Is In Chicago Mode
Change Sig Sil
The Sig Sil option allows the user to set the Automatic Signal Silence timer. This is
the length of time the signal circuits will operate before automatically silencing when
selected.
EXAMPLE: Entry of the number 3 would equal 90 seconds (3 x 30 sec.= 90sec.)
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
>2
Sig Sil Delay Is Set To:0 Min
Delay = Entry (0-10) x 30 Sec
Enter New Sig Sil Delay (0-10):
Change Ann
The change Ann option allows the user to enable and disable the supervision of the
supervised annunciator devices connected to the RS-232 port.
Change Menu 2
1=City 2=Sig Sil 3=Ann 4=Trbl
5=Dialer 6=Prefix 0=Exit
Press Enter Key To Exit
Press Any Other Key To Toggle
Remote Annunciator is Detached
Remote Annunciator is Attached
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...