Flex 620 System Operation - Revision 5, 11/22/01
_______________________________________________________________________________________________
20
Resound or
Return of
Signals
The signal silence switch is alternating action switch. If the user subsequently
presses the SIGNAL SILENCE switch again, the signal circuits will activate.
1. The lower yellow LED for the SIGNAL SILENCE switch will extinguish.
2. The yellow LED for the SIGNAL SILENCE switch will pulse.
3. All the output signal circuits which had de-activated will re-activate returning
the system status to the original alarm condition.
___________________________________________________________________________________________
Reset
After the initiating device(s) have been restored (i.e. cleared to normal condition),
the momentary
Reset
switch should be depressed. When the user presses the
RESET switch the following actions will occur:
1. All signal circuits will deactivate.
2. All output relays circuits programmed for "immediate reset" will deactivate
without delay (**
System default
**). The control panel will return to the
normal condition.
3. If any output relay circuits are programmed for sequential reset, the highest
circuit so programmed will de-activate first. Four seconds later the next
highest addressed programmed will de-activate. This pattern will continue
until all of the sequentially reset relays have been de-activated.
4. Power will be removed from all initiating input points for four (4) seconds to
restore any latched devices.
5. The RESET key's activation is logged into the History Buffer to provide a
time stamped record of the event's occurrence.
6. The control panel will re-enter into the normal quiescent condition.
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...