Flex 620 System Operation - Revision 5, 11/22/01
_______________________________________________________________________________________________
38
System I/O Components (600 Series)
Conventional
Input Module
The conventional input module (CIM) consists of up to 3 assemblies. The
I/O
Circuit module
, the
Style D (Class A) adapter
, and the
Alarm Display
. To view a
comprehensive listing of compatible devices with the Flex 620 control panel, refer to
Figure 3-3, Compatible Initiation Devices found at the end of this section. Also refer
to Figure 3-4, Compatible Auxiliary Devices for comprehensive listing of auxiliary
devices.
Circuit
Module
The circuit module provides four (CIM-4) or eight (CIM-8) conventional circuits.
All circuits operate on the Style B (Class B) mode of operation. The
End of Line
Resistor
(EOLR) required is 3.9k ohms with a maximum of 25 ohms line resistance.
Programming jumper (S1) is provided on each board for setting the vertical
position/address of the card (S1-1 through S1-4). The I/O circuit module uses the
lower terminal block and connects via cables to the bus driver module. The
conventional input module and its display require one bay of the F620 system.
Note: When the CIM-4 and CIM-8 circuits are programmed as AND zone types use
only Gamewell model 70133,70134 and 70135 detectors.
Style "D"
Adapter
The style D adapter card (CIM-SDA) provides 4 or 8 Style D (Class A) circuits to
the I/O circuit module. When the Style D adapter is used the EOLR's are not
required. The style D adapter uses the upper terminal block, and is cabled to the I/O
circuit module.
Display
Module
The display module provides eight (8) red circuit alarm LED's, eight (8) yellow
circuit trouble LED's. Eight (8) circuit tactile switches are provided for
programming
,
Bypass
and
WalkTest
functions. The display module connects (via
the display bus) to the bus driver module. The physical location of the display is set
by the addressing jumper S1. Ensure addressing jumper is set according to its
physical location in the cabinet and matches associated I/O module address jumper
setting. Refer to Figure I-1, Cabinet Module Locations.
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...