Flex 620 System Operation - Revision 5, 11/22/01
_______________________________________________________________________________________________
44
Building
Control Module
The building control module (BC) consists of three (3) assemblies. The
I/O Building
Control Module
, the
Building Control Expander,
and the
Building Control
Display/Switch Module.
Building
Control
Circuit
Module
The building control module consists of eight (8) form A/B (jumper programmable)
10 amp relays set up in four (4) "ON" relays and four (4) "OFF" relays, with a 10 amp
fused common. Each relay (ON and OFF) is programmable for N/O or N/C contacts
by removing the A or B jumper. Remove the A jumper for N/C contacts or the B
jumper for N/O contacts. The module also provides four (4) feedback input points
(switched negative) using 3.9K ohm resistors in parallel with an open feedback
contact. A (-) connected directly to the feedback point will actuate the Red LED and a
(-) through the 3.9k resistor will actuate the Green LED. Should the feedback points
be connected the LED's on the building control display will follow the status of the
feedback input point. Otherwise the LED's on the display will follow the status of the
active relay. Programming jumper (S1) is provided on each board for setting the
vertical position/address of the card (S1-1 through S1-4). The building control
module uses the lower terminal block and cables to the bus driver module. The
building control module uses one slot in the Module bus.
Building
Control
Expander
The building control expander module provides an additional eight (8) form A/B
(jumper programmable) 10 amp relays set up in four (4) "ON" relays and four (4)
"OFF" relays, with a 10 amp fused common. The module functions identically as the
building control module - providing four (4) feedback input points (switched negative)
using 3.9k ohm resistors in parallel with an open feedback contact. The expander
module mounts to the building control module (via standoffs) and uses the upper
terminal block and cables to the I/O building control module.
Building
Control
Display/Switch
Module
The control display module provides eight (8) red "OFF" relay activated LED's, eight
(8) green "ON" relay activated LED's. Eight (8) three (3) position (AUTO,ON,OFF)
rotary switches are provided for manual control of the I/O building control module
and building control expander. Eight (8) circuit tactile switches are provided for
programming
and
Bypass
functions. Card slots are provided for building control
description, comments. The building control display module mounts to the display
door and is cabled to the bus driver module. The physical location of the display is
set by the addressing jumper S1. Ensure addressing jumper is set according to its
physical location in the cabinet and matches associated I/O module address jumper
setting. Refer to Figure I-1, Cabinet Module Locations.
___________________________________________________________________________________________
ON
COM
ON relay
OFF relay
B
A
B
A
OFF
Figure 3.2 Typical building control circuit relay configuration
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...