Input Circuit
Type
(continued)
3. SIGNAL SILENCE
When in alarm the Signal Silence Circuit will Signal Silence the System
from a remote location. Each new alarm on the Signal Silence Circuit will
switch the system between de-active and active.
4. DRILL
When activated the Drill Circuit will Drill the system from a remote
location.
____________________________________________________________________________________________
Output Signal
Circuit Type
A. STEADY DC
Steady DC type signal circuit is the System Default. When Activated, any
signal circuits programmed for Steady DC will provide a 24VDC
uninterrupted output.
B. MARCHTIME 60
Marchtime 60 circuits, when activated, will provide a 24 VDC output on the
selected circuits at a 60 pulses per minute rate with a duration of 50% on and
50% off cycle.
C. MARCHTIME 120
Marchtime 120 circuits, when activated, will provide a 24 VDC output on
the selected circuits at a 120 pulses per minute rate with a duration of 50%
on and 50% off cycle.
D. TEMPORAL
Temporal signaling circuits, when activated, will provide a 24 VDC output
in the pattern of a Morse Code "U", this pattern is active for .25 seconds, off
for .25 seconds, active for .25 seconds, off for .25 seconds, active for .75
seconds, off for .75 seconds. The pattern repeats until the circuit is returned
to Idle.
E. CALIFORNIA UNIFORM FIRE CODE
California Uniform Fire Code Signal circuits, when activated, will provide a
24 VDC output in Marchtime 120 format for 10 seconds on and 5 seconds
off. The pattern repeats until the circuit is returned to Idle.
F. CODED
Zone coded signaling circuits when activated will produce a 24VDC pulsed
numeric code to be transmitted up to 6 times or as programmed. A separate
code is usually transmitted for each input zone.
Technical Manuals Online! - http://www.tech-man.com
Summary of Contents for FLEXALARM 620
Page 2: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 4: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 6: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 7: ...Technical Manuals Online http www tech man com...
Page 8: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 12: ...Technical Manuals Online http www tech man com...
Page 13: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 20: ...Technical Manuals Online http www tech man com...
Page 21: ...Section 2 FLEXALARM 620 System Operation Technical Manuals Online http www tech man com...
Page 34: ...Technical Manuals Online http www tech man com...
Page 35: ...This page intentionally blank Technical Manuals Online http www tech man com...
Page 64: ...Technical Manuals Online http www tech man com...
Page 65: ...Section 4 FlexAlarm 620 Programming Technical Manuals Online http www tech man com...