Radionics D6600 Setup
Digital Receivers Installation and Configuration
15
FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
2.3.3 D6600 Serial Communication Connection
Use the following figure to configure the cable that connects the Radionics D6600’s COM3 port to
a unused COM port on your Receiver Gateway capable Workstation computer. You can use a
standard null modem cable to connect the Radionics D6600 to the Receivers Gateway.
Figure 2.3 D6600 To Gateway Serial Connection
2.3.4 D6600 Setup
The default settings of the D6600 may be used with the following exception:
The Trailer (menu item 2.5.9 on the D6600) needs to be set to 0. Refer to the table below
for D6600 settings. For more detailed information, see the Radionics D6600 Program
Entry Guide.
Workstation
(Receivers Gateway)
D6600
Unused
COM
Port
COM
DB9 connector to non-dedicated
PC COM port
DB9 connector to
COM3 of D6600
5 - GND to 5 - GND
4 - DTR
3 - Tx
2 - Rx
6 - DSR
NOTE: Pins 4 and 6 connect to
each other on the PC end
2 - Rx
3 - Tx
Table 2.1 D6600/Receivers Gateway Configuration Settings
D6600 Menu Item
Menu Item Name/Description
D6600 Value for WAS Configuration
2.5.2
Baud
110 - 38400
2.5.3
Data Bit
8
2.5.4
Parity
0 - None
2.5.6
Link Test
30 seconds
2.5.7
Automation Wait
4 seconds
2.5.8
Header
00 No Header
2.5.9
Trailer
0D
2.5.15
Output Format
1 6500 format output
3.1.9.2
Receiver Type
0 Radionics
3.1.9.5
Output for Modem II/III Formats
0 Disable Network Automation Output
6.3.6
Network Automation Output Format
0 Disable Network Automation Output