Contact ID Reporting Formats
40
FocalPoint™ Receivers Gateway Installation & Operation Manual - P/N: 53251:Rev: A 9/8/09
602
TEST ###
G##TE###
GROUP##
Zone
Periodic test report
603
TEST ###
G##TE###
GROUP##
Zone
Periodic RF xmission
604
TEST ###
G##TE###
GROUP##
Zone
Fire test - User #
605
ZONE ###
G##ZO###
GROUP##
Zone
Status report to follow
606
ZONE ###
G##ZO###
GROUP##
Zone
Listen-in to follow
607
TEST ###
G##TE###
GROUP##
Zone
Walk test mode - User #
608
TEST ###
G##TE###
GROUP##
Zone
System Trouble Present
609
ZONE ###
G##ZO###
GROUP##
Zone
Video xmitter active
611
TEST ###
G##TE###
GROUP##
Zone
Point tested OK - #
612
TEST ###
G##TE###
GROUP##
Zone
Point not tested - #
613
TEST ###
G##TE###
GROUP##
Zone
Intrusion Zone Walk Tested - #
614
TEST ###
G##TE###
GROUP##
Zone
Fire Zone Walk Tested - #
615
TEST ###
G##TE###
GROUP##
Zone
Panic Zone Walk Tested
616
ZONE ###
G##ZO###
GROUP##
Zone
Service Request"},
621
ZONE ###
G##ZO###
GROUP##
Zone
Event Log reset
622
ZONE ###
G##ZO###
GROUP##
Control Panel
Event Log 50 full
623
ZONE ###
G##ZO###
GROUP##
Control Panel
Event Log 90 full
624
PANEL###
G##PA###
GROUP##
Control Panel
Event Log overflow
625
ZONE ###
G##ZO###
GROUP##
Zone
Time/Date reset - User #
626
PANEL###
G##PA###
GROUP##
Control Panel
Time/Date inaccurate
627
ZONE ###
G##ZO###
GROUP##
Zone
Program mode entry
628
ZONE ###
G##ZO###
GROUP##
Zone
Program mode exit
630
ZONE ###
G##ZO###
GROUP##
Zone
Schedule change
631
ZONE ###
G##ZO###
GROUP##
Zone
Exception schedule change
632
ZONE ###
G##ZO###
GROUP##
Zone
Access schedule change
633
DACR ###
G##DA###
GROUP##
Control Panel
Receiver Alarm Buffer Below 25%
634
DACR ###
G##DA###
GROUP##
Control Panel
Receiver Alarm Buffer Below 75%
635
DACR ###
G##DA###
GROUP##
Control Panel
Receiver Alarm Buffer Full
641
ZONE ###
G##ZO###
GROUP##
Zone
Senior Watch Trouble
642
ZONE ###
G##ZO###
GROUP##
Zone
Latch-key Supervision - User #
Table B.1 Contact ID Reporting Formats (Continued)