IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
95
Change Silence
Inhibit Delay
The Change Sil Inh option allows the selection of the time period in which Silence is
inhibited after an alarm signal.
Change Menu 3
1=Abort 2=Prefix 3=Config 4=Tally
5=Sil Inh 6=AutoSil 0=Exit
>5
Sil Inh Delay Is Set To: 0 Min
Enter New Signal Sil Delay (0-10)
Delay=Entry (0-10) X 30 sec
Change Auto
Silence Delay
The Change Auto Sil Delay option allows the selection of the time period after an alarm
which Silence automatically actuated.
Change Menu 3
1=Abort 2=Prefix 3=Config 4=Tally
5=Sil Inh 6=AutoSil 0=Exit
>6
Auto Sil Delay Is Set To: 10 Min
Enter New Signal Sil Delay (0-26)
Delay=2 min + Entry (0-26) X 30 sec