103
Test Menu
1=Input 2=Output 3=ID 4=Gnd
5=Lamp 6=Analog 0=Exit
>3
00=0C 01=FF 02=FF 03=FF 04=01 05=02
06=05 07=FF 08=FF 09=FF 10=FF 11=FF
12=FF 13=FF 14=FF 15=FF 16=FF 17=09
18=FF 19=FF 20=FF 21=FF 22=FF 23=FF
24=FF 25=FF 26=FF 27=FF 28=FF 29=FF
30=FF 31=FF 32=FF 33=FF 34=FF 35=FF
36=FF 37=FF 38=FF 39=FF
00=0C 01=FF 02=FF 03=FF 04=01 05=02
06=05 07=FF 08=FF 09=FF 10=FF 11=FF
12=FF 13=FF 14=FF 15=FF 16=FF 17=09
18=FF 19=FF 20=FF 21=FF 22=FF 23=FF
24=FF 25=FF 26=FF 27=FF 28=FF 29=FF
30=FF 31=FF 32=FF 33=FF 34=FF 35=FF
36=FF 37=FF 38=FF 39=FF
Test Gnd
The Gnd (Ground) test utilizes a unique method of ground detection. A measurement is
taken from the +5 supply to earth ground and a value is displayed. Then a measurement
from system common is taken and its value is displayed. The differential value between
these two measurements must be greater than 142 but less than 255 for a reading of
“Good”.
NOTE: The values displayed are derived from an A/D conversion and not displayed
in actual voltages.
Test Menu
1=Input 2=Output 3=ID 4=Gnd
5=Lamp 6=Analog 0=Exit
>4
Ground Fault Test
Press Enter Key To Exit
142 < Diff < 255
5V=216, Gnd=1, Diff=215 : Good
Test Lamps
The Lamp test feature will illuminate all of the system LEDs when selected. It will light
one panel at a time while alternating the internal sounder with each panel lit.
Test Menu
1=Input 2=Output 3=ID 4=Gnd
5=Lamp 6=Analog ork 0=Exit
>5
Press enter to continue
Technical Manuals Online! - http://www.tech-man.com