IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
108
ASCII Transfer
From the ASCII TRANSFER SETUP menu select option 6 to display the ASCII
TRANSFER SETUP menu. The following settings should be displayed.
ASCII UPLOAD
1) Echo locally ......... NO
2) Expand Blank Lines ... NO
3) Pace character ....... 0 (ASCII)
4) Character pacing ..... 15 (1/1000 sec)
5) Line pacing .......... 10 ( 1/10 sec)
6) CR translation ....... NONE
7) LF translation ....... STRIP
ASCII DOWNLOAD
8) CR translation ....... NONE
9) LF translation ....... NONE
SYSTEM MONITORING & CONTROL
Status
Monitoring
The computer can be used to monitor the status of the system. All status changes are
transmitted from the P1 port of the CPU, or the isolated ascii connectoin on bus card or
Iso-232 card. The data transmitted can provide detailed information on alarm, trouble and
system status changes. It can also aid in troubleshooting by providing detailed information
of system faults.
Access Levels
System access levels may be entered via the computer. By transmitting a carriage return
(
Enter
) to the system you will be prompted with “ ENTER PASSWORD” . By entering
the proper password you may set the system to it’s various access levels.
Control Strings
Certain control strings may be transmitted to the system that provide remote control of the
system from the computer. If the proper access level is enabled (see access levels) the
system can be acknowledged, the signals can be silenced or the system can be reset from
the computer. The following control strings provide these functions:
RESET = ^[Ox – F4
ACKNOWLEDGE = ^[OP – F1
SIGNAL SILENCE = ^[Or – F2
Most software communication packages will allow the function keys to be configured for
transmission of these control strings.