IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
121
Fire zones.
13=Verification zone
14=Do not use
15=Automatic zone
16=Style zone
17=And zone
20=Water zone
21=Watr zone
23=Watrs zone
B:
Device bypass state
0=Not bypassed
1 =Bypassed
1:
Dictionary 1 word (0-126)
2:
Dictionary 2 word (0-126)
3:
Dictionary 3 word (0-126)
4: Dictionary 4 word (0-126)
5:
Dictionary 5 word (0-1023)
Y:
Bypass Group Assignment
Output Device Variables
N:115 D:11 G:26 A:2 S:0 R:1 L:1 B:0 1:0 2:0 3:0 4:0 5:00 P:0 I:0 Y:0
N:
Device address/number
D:
Device type (F610/F632/F650 only)
0=Conventional Circuit
1=GW-Signal Sounder Audio (SCE-95)
4=GW—City Tie (CTX-95)
8=GW-Relay SPDT (RCE-95)
9=GW-Signal (SCE-95)
12=GW-Building Control (BCE-95)
17=F500 output Device
G:
Output group number (F610/F632/F650 only)
A:
Alarm activation level (0-3)
E:
Restoration type
0=Reset restore
1=Acknowledge restore
2=Signal Silence restore
Q:
Variable for conventional Relay or BC circuit else 0
If I=14,15,94,95 ie card is conventional Relay or BC type then
0=lnstantaneous reset
1 =Sequentially reset
Technical Manuals Online! - http://www.tech-man.com