IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
122
S:
Output Variable (default=0)
If D=4 (CTX-95)
0=Normal
1= Common Alarm
2=Supervisory
3=System Trouble
if I=1,48,53,54,55 ie card is a conventional signal type then
1=Steady ON signal
2=60 pulses/min, .50 sec ON/OFF
3=120 pulses/min' .25 sec ON/OFF
4=Temporal signal
5=California signal
6=Coded signals
7=Releasing
R:
Variable for Signal, BC conventional circuit else 0
if I=1.48.53.54.55 ie card is Signal type then
0=Signal ckt is not programmed for drill
1=Signal ckt is programmed for drill
if 1=14. 15 ie card is Relav or BC type then
0=OFF relay is programmed for open in auto mode
1=OFF relay is programmed for closure in auto mode
L:
Variable for Signal, BC conventional circuit else 0
if 1=1.48 53.54.55 ie card is Signal type then
0=Signal ckt is not programmed for auto signal silence
1=Signal ckt is programmed for auto signal silence
If 1=14. 15 ie card is Relay or BC
type
then
0=ON relay is programmed for open in auto mode
1 =ONrelay is programmed for closure in auto mode
B:
Bypass state
0=Device/ckt is not bypassed
1=Device/ckt is bypassed
1:
Dictionary 1 word (0-126)
2:
Dictionary 2 word (0-126)
3:
Dictionary 3 word (0-126)
4:
Dictionary 4 word (0-126)
5:
Dictionary 5 word (0-1023)
P:
Display Card number (12 - 15, 20 - 23, 28 - 31, 36 - 39) of associated
BCE/BCD, RCE/RCD or SCE/SCD combinations.
I:
Display Card switch and/or led position(0-7) of associated BCE/BCD,
RCE/RCD or SCE/SCD combinations.
Y:
Bypass Group Assignment