IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
123
Control by Event Table
This table consists of up to 256 lines that represent each of the possible Input Groups. Each set of two
characters in the line represents a Hexadecimal number. When these numbers are converted to Binary
and configured in rows from LSB to MSB each row represents an output group from 1 to 256. In
network systems, there will be separate CBE tables for each node in the network that will oprate
ouput groups on this panel.
N:xxx
N:xxx
A three digit number (0-250 leading 0s may be omited) identifying the node whos
input groups will activate outputs on this panel. A zero (0) indicates this panel, other numbers
indicate panel Node numbers of other panels connected to the network which are
programmed to activate outputs on this panel. Multiple CBE tables will exist only in network
systems.
I:xxx
I:xxx
A three digit number (0-255 leading 0s may be omited) identifying the Input group
number associated with the following Output group line
Dictionaries
The start and end of each of the 5 word libraries are delimited by two fore slash characters. Word
dictionaries 1-4 may have up to 126 entries and dictionary 5 may have up to 1023 entries. Entry 0 in each
dictionary should be left blank for default purposes.
//
Word dictionary 1, Entry 0
Word dictionary 1, Entry 1
|
Word dictionary 1, Entry 126(maximum)
//
Word dictionary 2, Entry 0
Word dictionary 2, Entry 1
|
Word dictionary 2, Entry 126(maximum)
//
Word dictionary 3, Entry 0
Word dictionary 3, Entry 1
|
Word dictionary 3, Entry 126(maximum)
//
Word dictionary 4, Entry 0
Word dictionary 4, Entry 1
|
Word dictionary 4, Entry 126(maximum)
//
Technical Manuals Online! - http://www.tech-man.com