Addendum for IF 600 Firmware Ver. 7.1
Issue A 9/27/01
6
Programmable Sounder Bases (Cont.)
ZONE TYPE TABLE - P2
Display Panel
Name
Description
Ver
Verification
Automatically verifies the device).
(Default program, after a 45 sec. Min., 60 sec. Max
Reset/Stabilization delay, monitors the device for 60
seconds to verify an alarm condition.
Auto
Automatic
Places the panel into General Alarm
AutSB Automatic
detector
with Sounder Base
Places the panel into General Alarm. The Sounder in
the base has the same group number as the detector,
and is a CBE programmable output. Activating
output group 254 will activate all Sounder Bases in
the system.
AutSBS Automatic
detector
with Sounder Base,
Silenceable
Same as AutSB, plus the Sounder in the base can be
silenced by SIGNAL SILENCE commands.
Gener
Generic
All the device control functions are active without
placing the system in a general alarm condition at
the panel.
And
And Initiating Zone
Two stage automatic detection.
Ack
Acknowledgment
Remote location acknowledgment
Drill
Drill
Remote drill system condition.
SigSil
Signal Silence
Remote location Signal Silence
Reset
Reset
Remote reset of the panel - resets system.
Abort
Abort
Delays or stops discharge cycle
Dump
Dump
Initiates discharge manually
Super
Supervisory
Sprinkler Supervisory signal input
Water
Water flow
Water flow, non silenceable
Watr
Water flow delayed
Water flow, delayed, non silenceable
Watrs
Water flow delayed
Water flow, delayed, silenceable