PN 72083
Issue A 2/7/2001
XP95-M Analog Addressable Multisensor Detector
Supplement to the Installation and Operation Manuals
For
The IF-610 (p/n 71810 issue 3 or higher), IF-632 (p/n 71906 Release: 2 or higher),
and the IDENTIFLEX 600 Stand Alone Panel firmware version r7 manual
supplement (p/n 71956 issue 1 or higher).
XP95-M Analog Addressable Multisensor Detector.
The Multisensor Detector includes both Photoelectric and Thermal sensing elements integrated into a
single head. The obscurity information from the Photoelectric sensor is combined with the rate of rise
information from the Thermal sensor, by a custom microprocessor, into the data count that is sent to the
FACP for processing. The microprocessor also performs drift compensation for the photoelectric sensor as
contaminants build up within the detection chamber. When the compensation reaches it’s set limits, the
microprocessor signals the FACP of the need to clean the detector. The microprocessor also monitors the
all of the internal functions of the detector and, if any problem arises, signals the FACP of a trouble.
Installation
The XP95-M installs in the standard Series 95 bases in the same manner as all of the other Series 95
Detectors.
Programming
The XP95-M has a nominal, fixed, sensitivity of 2.4%/ft., and compensation is accomplished within the
detector itself. When programming inputs, any device detected or programmed as an XP95-M will have the
word “
Multi
” in the
D_TYPE
location, and will not have the
SENS
or
COMP
selections available.
Ckt:XX Add:xxx D_Type:Multi Z_Type: xxx
I_Grp:x
WD:###
xxxxxx xxxxxxx xxxxxxxxx
xxxxxxxxxxx xxxxxxxxxxx
All other programming of the input is the same as other detectors.