IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
6
SYSTEM OVERVIEW
IF 610
Control Panel
The Gamewell. IF 610 is a microprocessor based fire alarm control panel. The IF
610 system is available in three configurations; a 126 point, one circuit
analog/addressable circuit control panel (IF 610-126), a 252 point, two circuit
analog/addressable circuit control panel (IF 610-252), and a 504 point, four circuit
analog/addressable circuit control panel (IF 610-504). The system is designed to
accommodate a wide variety of applications providing the user with a full range of
features including; self testing, self monitoring and full field programming capability.
The IF 610 system comes complete with a system housing, a main 6 amp power
supply, the operators display module and the analog addressable module (1, 2 or 4
circuits).
SYSTEM MODULAR CONSTRUCTION
Common Control
Section
The common control section (CCS) consists of three modules; the operators display,
the bus driver module, and the main CPU module.
Operators Display
Module
The operators display module (ODM) is the main user interface to the IF 610 system.
It includes the interactive alphanumeric display, LED indicators, and tactile switches.
The operators display module provides the user with visual indications and guided
prompts during all operating conditions. All alarms, faults, or supervisory actions, as
well as system operating conditions (
Normal, Alarms, Faults)
are shown on the
alphanumeric display. LED’s provide indication and prompt the user to respond to
the next sequential action. The "Power On" LED indicator is green, Alarms are
indicated by red LED's. Faults and user prompts are indicated by yellow LED's.
Bus Driver
Module
The bus driver module contains the circuitry that interfaces with the CPU and system
modules. The bus driver module is equipped with two Style Y or Z, limited energy
signaling circuits (2 amps maximum each), four relays which provide
Common
Alarm, Common Trouble and Supervisory
relays (Form c). A spare relay is provided
for future applications, and a city tie circuit. It has two power limited outputs for 24
Vdc auxiliary power, and resetable 24 Vdc smoke detector power. Circuitry to
monitor the status of the CPU and set the system in a default mode of operation is
also incorporated in the bus driver module. The (6) amp DC main power supply is
also incorporated into the Bus Driver Module.. The main power supply has a built in
battery charger and connections to the battery. This charger will monitor and
recharge 25 AH lead acid type batteries and has provisions for extending the life of
batteries. This is accomplished by eliminating the buildup of contaminants on the
plates. Provisions for "Brown Out" protection are functional when the main AC
power drops below a safe operating voltage level. An isolated RS-232 port is
provided to communucate with external systems and displays.
CPU Module
The CPU module (or microprocessor module) contains the system operating firmware
and non-volatile memory. It provides all the system memory and processing
functions as well as providing the local and remote communications and supervision.