IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
12
SIGNAL
SILENCE
The “Signal Silence” switch (SIGNAL SILENCE) will silence (i.e. return to
normal), any circuit or relay that is programmed to restore on Signal Silence.
The Signal Silence switch is an alternating action switch. Pressing the Signal
Silence switch will return the silenced circuits to an active state.
DRILL
The “Drill” switch (DRILL) will activate all circuits that have been
programmed to respond when the Drill switch is pressed. The Drill switch is
alternate acting, pressing the Drill switch again will deactivate the test.
DAY
The “Day” switch (DAY) places the panel in the day mode, and enables
Positive Alarm Sequence (PAS).
Keypad Switches
These switches are used for test and programming functions.
Arrow Keys
Use to scroll the alphanumeric display and assist the user during system
programming.
INDICATORS
ACKNOWLEDGE
The “Acknowledge” LED (red) will flash to indicate the next action is to press the
"ACK" switch.
RESET
The “Reset” LED's (red) will flash when the RESET switch is available for use.
SIGNAL SILENCE
The “Signal Silence” LED (red) will flash to indicate that the SIGNAL SILENCE
switch is active.
DRILL
The “Drill” LED (red) indicates the Drill feature has been activated.
DAY
The “Day” LED (yellow) indicates the system is in the day mode, and that Positive
Alarm Sequence (PAS) is active.
TROUBLE
DISPLAY
The “Trouble” LED (yellow) indicates the system is not in the normal condition, a
fault detected.
SUPERVISORY
DISPLAY
The “Supervisory” LED (yellow) indicates a supervisory zone has activated
(alarmed).
ALARM
DISPLAY
The "Alarm" LED (red) indicates a common fire alarm has been activated in the
system.
POWER ON
The "Power On" LED (green) indicates AC line operation. If pulsing, this indicates a
problem with the incoming AC line voltage, main or backup (battery) power supplies.
BATTERY
The “Battery” LED (yellow) indicates a battery fault such as low or missing battery
.
PRE ALARM
The “PreAlarm” LED (red) indicates that the system is in a first stage alarm
condition , such as in Positive Alarm Sequence (PAS).
SIGNAL
SILENCED
The “Signal Silenced” LED indicates that the signal circuits have been silenced
during an alarm.
Technical Manuals Online! - http://www.tech-man.com