IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
13
BYPASS
The “Bypass” LED indicates that points which have been programmed for bypass are
actually bypassed.
WALK
TEST
The “Walk test” LED indicates that the panel is in the walk test mode.
SYSTEM OPERATING CONDITIONS
Default Mode
WARNING NOTE
When shipped from the factory, the IF 610 system has been initialized to a
minimal "default" configuration as part of our system testing procedures. It is
important that the system be re-initialized utilizing the SmartStart feature upon
installation. This will result in a customized default configuration.
The IF 610 System will not recognize or communicate with any of the
connected devices until the SmartStart process has been exercised. The IF
610 will not report an alarm until this process has been completed. Refer to
the programming section of this manual for details about activating
SmartStart.
After the SmartStart routine has initialized the IF 610, the system will be configured
as follows:
1. All (input) initiating points are configured to be "Automatic" initiating points
(standard smoke detector points). Point Identification Devices (PID's) shall be
configured as manual stations if the priority interrupt is set.
2. The system defaults to Security Level #2 (Acknowledge, Signal Silence and
Reset Switches are accessible without a password).
3. Whenever any input point(s) goes into alarm:
A.
All output signaling circuits activate and produce a steady, 24VDC output.
B.
All output relays are activated.
C.
The city-tie and common alarm relays are activated.
Normal Quiescent
Condition (default)
When the system is in the normal quiescent condition, the green "Power On" LED is
illuminated indicating the system is operating from normal AC line power. All
input and output circuits are "normal" (no alarm or trouble conditions). All other
LED's and alphanumeric display are extinguished, the system internal buzzer is
silent. To view system status message, press "
Enter
". Refer to Figure O-1.
In the normal condition, the green "Power-On" LED will be 'ON' - steady. All other
indicators will be extinguished.
>>NOTE: The system is equipped with a built-in screen saver. When the system
remains in the idle mode (i.e. normal quiescent condition) for over 15 seconds
the screen will automatically go blank.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com