IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
15
Display for Multiple Alarm(s)
•
NOTE:
Multiple alarms are shown after the words ALARM Total
“x”; with “x” representing the total amount of alarms.
Status : ALARM Total X MM/DD/YY HH:MM
Fire Alarm in Ckt#_ Dev#:_
Figure O-3
OPERATING PROCEDURES
Acknowledging
the Alarm
Condition
When the user presses the "ACK" switch to acknowledge an alarm condition,
the following actions will occur.
1. The control panel's internal audible buzzer will (always) silence.
2. The acknowledge key's activation is logged into the History Buffer to
provide a time stamped record of the event's occurrence.
3. The Acknowledge red LED will extinguish.
4. Any outputs programmed to return to the normal condition upon pressing
the "ACK" switch will return to normal at this time.
5. The red LED's for RESET and SIGNAL SILENCE switches will flash.
This "guided prompt" feature notifies the user that the next expected action
is to
Reset
the system or
Silence
the signals (if so programmed).
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com