IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
66
ZONE TYPE TABLE - P2
Display Panel
Name
Description
Ver
Verification
Automatically verifies the device).
(Default program, after a 45 sec. Min., 60 sec. Max
Reset/Stabilization delay, monitors the device for 60
seconds to verify an alarm condition.
Auto
Automatic
Places the panel into General Alarm
Gener
Generic
All the device control functions are active without
placing the system in a general alarm condition at
the panel.
And
And Initiating Zone
Two stage automatic detection.
Ack
Acknowledgment
Remote location acknowledgment
Drill
Drill
Remote drill system condition.
SigSil
Signal Silence
Remote location Signal Silence
Reset
Reset
Remote reset of the panel - resets system.
Abort
Abort
Delays or stops discharge cycle
Dump
Dump
Initiates discharge manually
Super
Supervisory
Sprinkler Supervisory signal input
Water
Water flow
Water flow, non silenceable
Watr
Water flow delayed
Water flow, delayed, non silenceable
Watrs
Water flow delayed
Water flow, delayed, silenceable
DEVICE TYPE TABLE - P3
Display Panel
Description
Ion. Ionization
Sensor
Opt .
Photo-Electric Sensor
Heat Thermal
Sensor
Mon.
Point Identification Device (contact monitor)
Man.
Manual Station (or PID with priority interrupt set)
CZI
Collective Zone Interface
CZII
Collective Zone Interface (with priority interrupt set)