IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
70
Signal Circuit Types
Output
Signal Circuit
Type
A. STEADY DC
Steady DC type signal circuit is the System Default. When Activated, any
signal circuits programmed for Steady DC will provide a 24VDC
uninterrupted output.
B. MARCHTIME 60
Marchtime 60 circuits, when activated, will provide a 24 VDC output on the
selected circuits at a 60 pulses per minute rate with a duration of 50% on and
50% off cycle.
C. MARCHTIME 120
Marchtime 120 circuits, when activated, will provide a 24 VDC output on
the selected circuits at a 120 pulses per minute rate with a duration of 50%
on and 50% off cycle.
D. TEMPORAL
Temporal signaling circuits, when activated, will provide a 24 VDC output
in the pattern of a Morse Code "U". This pattern is active for .25 seconds,
off for .25 seconds, active for .25 seconds, off for .25 seconds, active for .25
seconds, off for .75 seconds. The pattern repeats until the circuit is returned
to Idle.
E. CALIFORNIA UNIFORM FIRE CODE
California Uniform Fire Code Signal circuits, when activated, will provide a
24 VDC output in Marchtime 120 format for 10 seconds on and 5 seconds
off. The pattern repeats until the circuit is returned to Idle.
F. CODED
Zone coded signaling circuits when activated will produce a 24VDC pulsed
numeric code to be transmitted up to 6 times or as programmed. A separate
code is usually transmitted for each input zone.
G RELEASING
Releasing coded signaling circuits will sound at 60 bpm during one alarm,
120 bpm during pre-release, and steady during discharge and the discharge
delay if programmed.