IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
73
Initializing an
analog Circuit
Initializes an individual circuit. Allows the user to add new devices (detectors)
or remove devices in the specific circuit selected. All other circuit information
previously entered (utilized in Control By Event data base programming) is
protected and cannot be altered or damaged.
1. From the circuit programming display menu, select the [3] numeric key.
2. Press
"
Enter
"..
3. Select the circuit to initialize (1-4). SmartStart
feature configures new
data base making any changes that have been detected. See Figure 12D.
Polling Card XXX Circuit XXX Address XXX
Figure 12D
CONTROL BY EVENT
Control-by-Event programming allows the user to create a matrix whereby selected groups of
input devices are logically connected to selected groups of output devices or circuits. The
SmartStart feature automatically assigns all input devices to select all output devices or
circuits.
In the device specific screens, input or output group numbers (1 - 256) can be assigned to
each device. Multiple devices can be assigned to a single group but each device can only be
assigned to one group.
In the output programming menu for each device or circuit there is a field (Alr) for assigning
the Alarm level it will activate. The four levels of alarm, 0= pre-alarm, 1=1
st
alarm, 2=2
nd
alarm and 3=Rleasing. These levels combined with the CBE table determine when the circuit
or device will activate.