IF 610 Installation and Operation Manual
Issue 3, 10/04/00
Firmware Ver. 7
87
Change Code
The codes in the IF 610 systems are assigned to the input groups. When a device within
that group alarms, that code would be sounded on the signal circuits that have been
programmed as coded circuits. Each input group may be assigned an individual code that
contains up to 6 digits. The digits are defined in hexadecimal and range from 0-9 and A-F.
When selected each digits (1-6) of the code is entered individually.
After the code has been entered a sub-menu appears. This menu allows you to change the
Timing, the number of Cycles and the output of the signal circuits after the code is
complete, silence or March Time signal.
Change Menu 1
1=Pass 2=Code 3=Date 4=Seq
5=Baud 0=Exit
>2
Enter Input Ckt/Group Number:1
Current Code For Ckt/Group1=123456
Enter Digit 01:656565Re-enter Input :6
Enter Digit 02:5
Enter Digit 03:4
Enter Digit 04:3
Enter Digit 05:2
Enter Digit 06:1
New Code For Ckt/Group1=654321
Enter Input Ckt/Group Number:
Change Coded Signal's Parameters
1=Timing 2=Cycles 3=Signal
0=Exit
>1
Change Coded Signal's Timing
1=0.5 2=1.0 3=1.5 4=2.0
0=Exit
>2
Enter # of Cycles (1-8):
>3
Choose Signal
1=OFF 2=March Time
0=Exit