IF 632 Installation and Operation Manual
Release: 3 01/31/01
132
Change
Discharge Delay
The Change Dump option allows the selection of the time delay from the Discharge
command to the actual Discharge..
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
>4
Discharge Delay Is Set To: 0 sec
Enter Discharge Delay (0-30 sec):
Change
Dictionary
Changing the dictionary entries can be achieved by two means, changing the words or
uploading an entirely new dictionary. The upload function should only be accomplished
throug a P. C. connected through the serial port, or from the Master in a network.
Change Menu 4
1=Cfg 2=Water 3=Relse 4=Dump
5=Dict 6=Card 0=Exit
>5
Change Dictionary Menu
1=Words 2=Upload 0=Exit
Change
Dict.Words
To change the Dictionary words, select 1 from the Change Dictionary Menu. The system
will prompt you with the dictionary and word number to be changed. The existing word is
then displayed. To change the word, type the desired text or press enter to leave the
existing text and return to the word number prompt.
Change Dictionary Menu
1=Words 2=Upload 0=Exit
>1
Enter Dictionary #:1
Enter Word #:1
Overwrite Current Word:
Fire Alarm
Enter New Word:
Enter Word #:22
Word Doesn’t Exist, Append New Word
Enter New Word:
Enter Word #: