IF 632 Installation and Operation Manual
Release: 3 01/31/01
140
BIT1
BIT 2
BIT 4
XP-95P
Local LED
Test Mode
Remote LED
XP-95I
Local LED
Test Mode
Remote LED
XP-95T
Local LED
Test Mode
Remote LED
MS-95
Local LED
N/A
N/A
PID-95
Local LED
N/A
N/A
CZI-95
Local LED
Class “A” Relay
Zone Power Off
RCE-95
Local LED
N/A
Relay
SCE-95
Local LED
N/A
Signal Power
Figure 1: Output Control Bits
Display Panel
Description
Trouble / No
Feedback
Background Dirty
Pre-Alarm
on 1st
Alarm / Shorted
Ion Ionization
Detector
0 - 9
10 - 40
41 - 44
Background
+
26
Background
+
36
Opt. Photo
Detector
(non-comp.)
0 - 9
10 - 40
41 - 44
25 +
(sensitivity * 6)
+ 8
25 +
(sensitivity * 6)
+ 18
Opt.
Photo Detector
(Compensated
)
0 - 9
10 - 40
41 - 44
Back
(sensitivity * 6)
+ 8
Back
(sensitivity * 6)
+ 18
Heat Thermal
Detector
0 - 7
10 - Fixed
Value
NA NA
Above Fixed
Value
CZI or CZII
CZI-95
0 - 16
17 - 54
NA NA
55 - 122
2nd Alarm
above 122
PID or MAN
PID - 95 or
MS - 95
0 - 9
10 - 54
N/A
N/A
55 - 127
REL
RCE - 95
0 - 14
15 - 45
NA NA
46 - 127
RSM
RSM-95
0 – 14
15 – 45
NA NA
46 - 127
SCE or Snd.
SCE - 95
0 - 14
15 - 45
NA NA
46 - 127
Figure 2: Device Count Threshold
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com