Addendum for IF 600 Firmware Ver. 7.1
Issue A 9/27/01
3
GENERAL
This addendum contains the information required to utilize new features and functions incorporated into
Version 7.1 of the IF 600 operating firmware. When using these features, follow the instructions contained
in this addendum.
All of the features and functions described in the manual that accompanied the system are unchanged
and perform as described in the original manual(s).
NEW FEATURES
XP95-M Analog Addressable Multisensor Detector.
The Multisensor Detector includes both Photoelectric and Thermal sensing elements integrated into a
single head. The obscurity information from the Photoelectric sensor is combined with the rate of rise
information from the Thermal sensor, by a custom microprocessor, into the data count that is sent to the
FACP for processing. The microprocessor also performs drift compensation for the photoelectric sensor
as contaminants build up within the detection chamber. When the compensation reaches it’s set limits,
the microprocessor signals the FACP of the need to clean the detector. The microprocessor also monitors
all of the internal functions of the detector and, if any problem arises, signals the FACP of a trouble.
Installation
The XP95-M installs in the standard Series 95 bases in the same manner as all of the other Series 95
Detectors.
Programming
The XP95-M has a nominal, fixed, sensitivity of 2.4%/ft., and compensation is accomplished within the
detector itself. When programming inputs, any device detected or programmed as an XP95-M will have
the word “
Multi
” in the
D_TYPE
location, and will not have the
SENS
or
COMP
selections available.
Ckt:XX Add:xxx D_Type:Multi Z_Type: xxx
I_Grp:x
WD:###
xxxxxx xxxxxxx xxxxxxxxx
xxxxxxxxxxx xxxxxxxxxxx
All other programming of the input is the same as other detectors.