IF 632 Installation and Operation Manual
Release: 3 01/31/01
94
Hardware Reset (continued)
5. After a 15 second delay, the system commences a hardware restart. Modules and
devices are being read and will scroll up on the display, Figure 3C. Next the System
RESET screen is shown, Figure 2A. Then the "System Idle" screen is displayed,
Figure 4.
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Polling Card XXX Circuit XXX Address XXX
Figure 3B
>>
NOTE: Upon completion of the SmartStart process, all
connected addresses will be contained in system memory
and all inputs will be tied to all outputs. Any input in
Alarm will activate the system outputs.
System Idle Display
After the initial system startup or system re-configuration is completed, the display will
show the current date (month/day/year) and time (military), see Figure 4.
>>
NOTE: The system is equipped with a built-in screen
saver. When the system remains in a idle mode (i.e.
normal quiescent condition) for over 15 seconds the screen
will automatically go blank.
Status :Normal
XX/XX/99 xx:xx
System Idle
Figure 4
PASSWORD ENTRY - ACCESS LEVELS
Four levels of password protection have been incorporated in the IF 632 system
firmware. These passwords allow access to various functions of the system.
Each of the four levels default to certain functions of the system and can be re-
assigned to other functions via programming. Up to ten passwords may be
assigned to these access levels. As well, an area to assign a user ID to each
password has also been provided for quick reference. Each user ID may
contain up to 10 characters. Each of these password ID’s may be assigned up
to a ten character string.