IF 600 Firmware Version R7 Manual Supplement
Issue 1 06/16/2000
13
Overview
Walk Test, Bypass mode, Detector/Device Test, and information displays can be
selected at any time from the Password Protected - Access Level 3. Function
Programming Menu by pressing one of the
FN
keys on the left or right arrow
keys, and selecting the desired test as indicated on the LCD screen.
1.
Make sure that a level 3 pass word has been entered
2.
From the Operational Mode press the key marked ‘
FN
’.
Function Programming
1=Walk Test 2=Bypass 3=Input Test
4=Output Test 5=Display 0=exit
Walk Test
Walk Test is an automatic test used to test devices in the system both silently and
audibly. Testing the system in the Walk Test mode enables one person to test the
system without the aid of another to confirm activation and reset the panel.
Activation (i.e. detected ALARM or TROUBLE signal) in the initiating device
will cause the panel to log the event and activate all associated indicating circuits
if programmed. The device is reset after four (4) seconds. Activation of a Fault
(Trouble) follows the same routine. For ALARM testing all associated signal
circuits will sound twice. For TROUBLE testing, all associated signal circuits
will sound once.
>>
NOTE: All devices selected for Walk Test become disabled and
will not ALARM. Devices not selected for Walk Test will
report an ALARM condition. After 30 minutes of inactivity the
system will time out of Walk Test.
1.
From Function Programming Display, press the “
1
” key followed
by the “
Enter
” key
2.
2. The
Walk Test
LED will begin flashing at 60 PPM. Figure T4
is now displayed.
Function Programming
1=Walk Test 2=Bypass 3=Input Test
4=Output Test 5=Display 0=exit
>1
Walk Test Menu
1=Display 2=Program
3=Exit
Figure T4
3.
Select “Display” [1] to display the circuits (input and output) that are currently in the
Walk Test mode. Select “Prog” [2] to select circuits for Walk Test mode.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...