System I/O Components
Analog
Addressable
Module
The analog addressable module is a 1 or 2 circuit card that monitors and controls up
to 126 analog/addressable devices (points) per circuit for a total of 126 or 252 points
per module. The analog interface module has its own microprocessor which
simultaneously communicates with the connected field devices and with the main
CPU. Each analog/addressable circuit can be wired as a Style 4 (class B) or, Style 6
(class A) analog/addressable circuit.
Analog
Expansion
Module
For the IF630-252, the optional expansion module (AAM-630E) provides 2
additional analog addressable circuits allowing a total of 504 devices to be connected
to a system.
____________________________________________________________________________________________
Main Power
Supply
The main power supply is an eight (8) amp DC supply. The main power supply has
provisions for a battery charger module and connections to the battery. Provisions
for "Brown Out" protection are functional when the main AC power drops below a
safe operating voltage level. Operating from a 120 VAC source, the main power
supply mounts in the lower left hand corner of the cabinet, and cables to the bus
driver module.
Lead Acid
Battery Charger
Module
The battery charger module is a plug-in type module and installs directly into the
main power supply card. This module will monitor and recharge 60 AH lead acid
type batteries and has provisions for extending the life of batteries. This is
accomplished by eliminating the build-up of contaminants on the plates.
____________________________________________________________________________________________
Addressable
Input Devices
The IF630 system is designed to operate with Gamewell's complete line of analog
detectors (ionization, photoelectric) and with the IdentiFlex 600 series of
Addressable Input Devices. These input devices are available as either a single Point
Identification Device (PID-95) or as a manual pull station (MS-95). The addressable
input devices provide the means for communicating between the IF630 analog circuits
and contact devices or conventional type smoke detectors. Both the PID-95 and the
MS-95 devices are field programmable.
Summary of Contents for Smart Start IDENTIFLEX 630
Page 2: ......
Page 4: ......
Page 6: ......
Page 11: ...Section 1 IDENTIFLEX 630 System Description...
Page 14: ......
Page 44: ......
Page 117: ...Section 1 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Introduction...
Page 123: ...Section 2 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Special System Functions...
Page 127: ...Section 3 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT System Test Mode...
Page 141: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Programming...
Page 201: ...Section 4 IF 600 FIRMWARE VERSION R7 MANUAL SUPPLEMENT Configuration File...